Dedicated Purpose Sensors
Proven to be highly reliable due to our advanced technology.
Our flame detector serves to ensure safe operation of boilers and gas turbines at the thermal power plant. Our detectors are designed to perform quick and accurate detection of burner ignition or flame loss, and can monitor flames of many types of fuels.
Flame Detectors
High quality, reliability, and safety of our dedicated sensors are proven in our Flame Detectors for Boilers and Gas Turbines, etc.
IR-S TYPE INFRARED FLAME DETECTOR
Net IR-S TYPE INFRARED FLAME DETECTOR
INFRARED FLAME DETECTOR RAIL MOUNTING NET IR-S
Image Flame Detector (OPTIS)
Features
Captures and processes the burner flame image through the CCD camera, and identifies the flame On/Off by its brightness and shapes. Using the CCD camera, it extracts and processes only the flame image data captured from a wide area, which can provide a very reliable detection and data from flame monitoring.
Photo
*Please contact the nearest Mitsubishi Power agency.
Flame Detector for Gas Turbines
Overview
This product inherits an IR-S type Infrared Flame Detector technology, which has been employed in many boilers at thermal power plants. Reliable photo diode is used for the sensor. By filtering incident light from furnace heat, it becomes possible for the detector to be unaffected by heat and focus on only near ultraviolet.
Photo
*Please contact the nearest Mitsubishi Power agency.
General-purpose Ultra Violet Flame Detector (YOKA-FD)
Overview
This product inherits an IR-S type Infrared Flame Detector technology, which has been employed in many boilers at thermal power plants. In addition to the explosion proof sensor, we also offer a light weight/compact size non-explosion proof sensor, which can be used depending on the location of your equipment. Our compact size sensor can be installed easily on DIN rail.
Features
- Stable detection of flames, which are generated from various fuels (Gas & oils).
Wave detection Range matches to the near ultra violet light wavelength generated by either gas or oil. - Detection of Low NOx Flames
With the wider detection wavelength, it achieved the lower affect from the atmosphere detection which occurs at the time of low NOx combustion. - Long Operation Lifetime
We have achieved the longer lifetime by adopting a semiconductor for sensor and high reliable parts for other sensor amplifier circuit.
Photo
Specification
- Sensor
Description | Specification | |
---|---|---|
Detection Wavelength area | 280 - 380nm | |
Ability of light identification | Not detected the radiant heat of 1000 deg C | |
Operating Temperature | -20 - +125 deg C | |
Sensor Output Signal | DC0 - 10V | |
Power Supply | DC12V(supplied by flame detector unit) | |
Size & Weight | Non Explosion Proof | Outer Diameter φ76mm x 120.5mm(L), Approx. 0.74kg |
Explosion Proof | Outer Diameterφ130mm x 231mm (L),Approx. 3kg |
- Flame Detector Unit
Description | Specification | |
---|---|---|
Output Signals | Flame ON | 1a |
Power Normal | 1a | |
Maximum value of contact current | 0.65A (DC125V) | |
Operating Temperature | 0 - +60 deg C | |
Flame brightness Level Output | DC0 - 11V | |
Power Supply | AC85 - 265V(47 - 440Hz) DC110 - 340V |
|
Dimension | 150mm (H) x 130mm (W) x 105mm (D) |
Flame Supervisor(MIRNDA-FD)
Overview
MIRNDA-FD is an industrial furnace flame supervisor which complies with Japanese Industrial Standard, JIS B 8415-2008 (revised in Nov. 2008).
This product has a fuel valve shutdown function for safety control, in addition to flame detecting function.
Features
- MIRNDA-FD is an industrial furnace flame detector that complies with the safety regulation JIS B 8415:2008.
- Consists of a flame detector and a safety control system (Fuel shutdown valve operation).
- Safety start-check sequence, which confirms flame existence before furnace ignition.
- Self-cheak function (normal action check can be done more than once per day)
- Semiconductor element sensor. The long operation lifetime by adopting high quality components besides the sensor itself.
- Self-cheak function is processed through the electric circuit. No shutter maintenance for mechanical parts is required.
- Various type of flame (by gas or oil) can be detected.
Detection wavelength bandwidth is conformed to the emission wavelength near ultra violet bandwidth, which is generated by either gas or oil. Therefore, this sensor can detect both types of flame, and is applicable for many types of fuel.
- Detection of Low NOx Flames
With the wider detection wavelength, it achieved the lower affect from the atmosphere detection which occurs at the time of low NOx combustion.
Photo
Specification Overview
- Sensor
Description | Specification |
---|---|
Detection Wavelength area | 280 - 380nm |
Ability of light identification | Not detected the radiant heat of 1000 deg C |
Self-check Function | Sensor circuit is entered periodically zero signal by flame supervisor unit. At that time, flame supervisor unit determines “Flame off”. |
Operatingt Temperature | -20 - +125 deg C |
Power Supply | DC12V(Supplied from flame supervisor unit) |
Size & Weight | Outer diameter φ76mm x 120.5mm(L), Approx. 0.74kg |
- Flame supervisor unit
Description | Specification | |
---|---|---|
Output Signals | Ignition trans ON | 1a |
Pilot Valve Open | 2a | |
Main Valve Open | 1a | |
Flame ON | 1a | |
Alarm | 1a | |
Maximum value of contact current | Alarm | 3A (AC250V , DC30V) |
Others | 10A (AC250V , DC30V) | |
Input Signal | Interlock Signal x 1 Start-up Command x 1 Lockout Reset x 1 |
|
Operating Temperature | 0 - +60 deg C | |
Communication Type | USB / EIA485 (switchable) | |
Flame Brightness Level Output | DC0 - 11V / DC4 - 20mA (switchable) | |
Power Supply | AC85 - 265V (47 - 63Hz) | |
Size |
|